dc.description.abstract |
Este trabalho tratou de avaliar o funcionamento de um filtro lento com retrolavagem automática (FLRA) sem energia elétrica, por meio do monitoramento da qualidade da água e do funcionamento da retrolavagem automática. O objetivo foi considerar a utilização do filtro para o tratamento de água de abastecimento em escala domiciliar, de forma especial em comunidades rurais. O filtro lento era coberto, de escoamento descendente, carga hidráulica variável, operando a uma taxa de filtração de cerca de 4 m³/m².d. Coletas diárias foram feitas para aferição dos parâmetros turbidez, cor aparente, cor verdadeira e oxigênio dissolvido, e a observação da retrolavagem era realizada no final das carreiras de filtração. O filtro removeu turbidez e cor aparente na faixa de 60% a 65%, e a remoção da cor verdadeira foi nula. O oxigênio dissolvido sofreu uma redução de 50% a 85% na filtração, indicando atividade microbiológica no leito filtrante. O sistema de retrolavagem automática funcionou corretamente, promovendo ao final de cada carreira de filtração o seu acionamento, limpando o leito filtrante como esperado. Por este estudo, conclui-se que o sistema automático do filtro é eficiente, porém precisa de ajustes para funcionar de forma mais branda, a fim de que tenha maior durabilidade. A eficiência da filtração foi abaixo da esperada, todavia com o aperfeiçoamento da alimentação do filtro isto pode ser remediado. |
pt_BR |
dc.description.abstract |
This research intended to evaluate the functioning of a slow sand filter with automated backwash (FLRA), using no electric power, by monitoring the water quality and automated backwashing system. Its objective was to consider the filter use for the supply water treatment in smaller home scale, especially in rural areas. The filter was covered, had descending flow, variable hydraulic load, operating with a filtration rate of about 4 m³/m².d. Daily sampling were made for measuring turbidity, apparent color, true color, and dissolved oxygen, and the backwashing observation was made at the end of the filtration career. The filter was able to remove turbidity and apparent color in about 60% to 65%, and the true color was not removed. Dissolved oxygen was reduced by 50% to 85%, showing microbiological activity in the filtering media. The automated backwashing system worked correctly, promoting its actuation at the end of each filtration career, cleaning the filtration media as expected. Through this study, it was concluded that the automatic system of the filter is efficient, but it need some upgrades so that it can work smoothly and be more durable. The filtration efficiency was lower than expected; however by fixing the feeding system this can be improved. |
pt_BR |
dc.format.extent |
46 f. |
pt_BR |
dc.language.iso |
por |
pt_BR |
dc.publisher |
Florianópolis, SC. |
pt_BR |
dc.subject |
|
|
dc.subject |
Slow Sand Filtration, Automation, Water Quality. |
pt_BR |
dc.subject |
Filtração lenta |
pt_BR |
dc.subject |
Automação |
pt_BR |
dc.subject |
Qualidade de Água |
pt_BR |
dc.title |
Avaliação do Funcionamento de um filtro Lento com retrolavagem Automática para o tratamento de Água de abastecimento em pequenas comunidades |
pt_BR |
dc.type |
TCCgrad |
pt_BR |
Files in this item
This item appears in the following Collection(s)
Show simple item record
Search DSpace
Browse
-
All of DSpace
-
This Collection
My Account
Statistics
Compartilhar